Solar energy storage system is an important technology and basic equipment to support the new power system, which has strict certification standards and entry thresholds in different countries and regions.
China Energy Storage Battery and System Certification:
1.Energy storage battery safety GB/T 36276, YD/T 2344.1, YD/T 2344.2
2.Energy storage system safety GB/T 36558, GB/T 34131
3. Inverter, converter GB/T 34120, NB/T 32004
4. Grid connection requirements GB/T 36547, GB/T 36548
U.S. and Canadian energy storage battery and system certification:
1. Energy storage battery safety UL 1973 (home storage), UL2743 (portable)
2. Energy storage system safety UL 9540
3. Energy storage system thermal runaway test UL 9540A
4. Inverter, converter UL 1741, UL 1741-CSA, CSA C22.2 No 107.1-01
5. Grid connection requirements IEEE1547, IEEE1547.1
6.Software Functional Safety Assessment UL 60730-1, UL 1998
7.FCC SDOC FCC Part 15
8.Energy efficiency CEC-300
European Energy Storage Battery and System Certification:
1.Energy storage battery safety IEC/EN 62619, IEC/EN 63056
2. Energy storage battery performance IEC/EN 62620, IEC/EN 61427-1/-2
3. Energy storage system safety IEC/EN 62040-1, IEC/EN 62477-1, IEC/EN 62368-1
4. Risk assessment of the safety of energy storage systems IEC/EN 62933-5-2
5. Inverters, converters IEC/EN 62109-1/-2, IEC/EN 62477-1
6. Safety of domestic energy storage in Germany VDE 2510-50
7.EMC IEC/EN 61000-6-1, IEC/EN 61000-6-2, IEC/EN 61000-6-3, IEC/EN 61000-6-4
8.ROHS Directive 2011/65/EU
9.Energy efficiency IEC/EN 61683, IEC/EN 50530
European grid connection requirements for energy storage batteries:
1.Germany VDE-AR-N 4105, DIN VDE V 0124-100, VDE-AR-N 4110, VDE-AR-N 4120
2. Italy CEI 0-21, CEI 0-16
3.UK G98(<=16A), G99(>16A)
4.France UTE C15-712-1, VDE 0126-1-1, XP C15-712-3 ,VFR 2019
5. Spain NTS 631, RD661, RD1699, UNE 206007-1:2013 IN, UNE 206007-2:2014 IN
6. Denmark TR 3.2.1, TR 3.2.2, TR 3.3.1
7. Austria OVE R25
8.Belgium C10/11
9.Other EU countries EN 50549-1, EN 50549-2, IEC61727, IEC62116
Australian Energy Storage Battery and System Certification:
1. Energy Storage Battery Safety AS/IEC 62619 + AS 62368.1
2. Energy Storage System Safety AS 62040.1.1 or IEC 62040-1
3. Inverter, converter AS 4777.2 or IEC 62109-1/2
4. Software evaluation AS/NZS 60335.1 Clause 22.46 or UL1973
5. Grid connection requirements AS/NZS 4777.2
Others
1. Lithium battery UN38.3: suitable for the scope of almost involving the world, belonging to the safety and performance testing, the United Nations for the transport of dangerous goods specifically developed for the United Nations Manual of Tests and Criteria for the Transport of Dangerous Goods, Part 3, paragraph 38.3.That is, the lithium battery is required to pass the height simulation, high and low temperature cycle, vibration test, impact test, 55 ℃ external short circuit, impact test, overcharge test, forced discharge test before transporting to ensure the safety of lithium battery transport.If the lithium battery is not installed with the equipment, and each package contains more than 24 cells or 12 batteries, it must also pass the 1.2 metres free fall test.
2. Air / sea transport identification report: from China (except Hong Kong) with battery products, the final air transport identification report must be directly authorised by the General Administration of Civil Aviation of China accredited by the Dangerous Goods Identification Agency for examination and certification.
ADAYO hybrid inverters ED5000, 800w microinverters ID800A have been certified for grid connection in most European countries.